FCP "Tiras-8P"

       The device is designed for continuous 24 hours operation as part of fire alarm systems in buildings with controlled climatic conditions. The device has eight zones to connect unaddressed fire detectors with constant current control, which can connect up to 32 detectors.

Описание, характеристики продукта

The device performs the following:
1.Control of the detectors as a normally closed and normally open contact with;
2.Management of sound and light and sound sirens;
3.Generation of signals to turn off ventilation and smoke removal;
4.Generation  signals to control fire-fighting devices ;
5.Transmission of notices to the central control monitoring  through the relay contacts "failure" and "fire" or by the dialer  module ( MCA module- More than 150 notices).
Main features:
- has stabilized voltage in zones that are not dependent on battery condition, which makes easy the design of the system and increases the maximum number of 2-wire detectors in each zone;
-relay output for powering 4-wire detectors with  current to 1 A;
relay output for alarms with a current switching up to 5A, and the ability to power from an external source;
- battery capacity of 7 A /h
-it has three verification algorithm for detectors operation.
Technical characteristics:
Information capacity of 8 zones
Operational temperature range from - 50C to +40 0 C at a relative humidity of 93%.
Overall dimensions 226 mm x 281 mm x 85 mm
Level of protection IR 30
Average life at least 10 years
Power supply   (187-242) V / 50 Hz in redundant electrical power
output voltage   (9,5 – 13,8)
 Battery 12 V, a capacity of 7 A / h.
Automatic Battery Charger, 100% charge - no more than 72 hours.
Current consumption from the battery FCIS "on duty" - 130 mA, the "fire" - 170 mA.
Protecting the battery from deep discharge is present, turning off the load at 10.5
Load current release of "+12", mA, not more 1000
The voltage in the zones  (11,0- 12,5)
Exit "notification" (relay) less than 5 A
Interfaces MRL-2.1,2 : MCA, MCA-GSM-1, RS485- Tiras 16.64 P