FCP "Tiras-16P"

The device is designed for continuous clock operation as part of fire alarm systems in buildings with controlled climatic conditions.
The device has sixteen zones for non-address to connect fire detectors with constant current control, which can connect up to 32 detectors.

Описание, характеристики продукта

The device performs the following:
1.  Control of the detectors as a normally closed and normally open contact with;
2.  Management of sound and light and sound sirens;
3. Generation of signals to turn off ventilation and smoke removal;
4.  Generation of  signals to control  fire-fighting devices;
5.  Transmission of notices to the central control monitoring through  the relay contacts "failure" and "fire" or by the dialer  module ( MCA - More than 150 notices).
 Main features:
1. The device  has stabilized voltage in zones that are not dependent on battery condition, which makes easy the design of the system and increases the maximum number of 2-wire detectors in each zone;
2.  Four relay outputs for powering 4-wire   four relay outputs for powering 4-wire detectors with a current switching up to 1.5 A and the possibility of supply from an external source;
3.  Relay output for alarms with a current switching up to 5A, and the ability to power from an external source;
4.  Battery capacity of 18 A/h;
5. It has three  algorithm of  verification for detectors operation.
Technical characteristics:
1. The information capacity of 16 zones
2. Operational temperature - 50C to +40 0 C at a relative humidity of 93%.
3. Overall dimensions – 331 mm x 410 mm x 85 mm
4. Level of protection – IR 30
5.The average life - of at least 10 years
6.Power supply  (187-242) V / 50 Hz in redundant electric power.
7.Output voltage – (9.5 – 13.8)
8.  Battery 12 V 18 A/h
9.Charger – automatic, 100% charge - no more than 72 hours.
10.Current consumption from the battery is not more than 120 mA
11.  Protecting the battery from deep discharge is present, turning off the load at 10.5
12.Load current release of "+12", mA, not more than 330
13. Stub power supply voltage (8.8 – 12.6)
14.  Exit "notification" (relay) is not more than 1.5 A
15.  Interfaces – MRL-2.1 – 2, MRL – 2, MCA, MCA-GSM – 1, RS 485- Tiras 16.64